CK60 Floor Standing
CK60 boilers are made from Grade GG20 cast iron and conform with the requirements of EN 303-1.
CK60 cast iron sectional boilers are designed for use in either open vented or pressurised heating systems up to 8 bar working pressure with gas, oil or dual fuel burners. There are seven models in the range 600 kW to 1200 kW. These are 3-pass boilers, ensuring that they comply with the efficiency requirements of ADL2B of Part L 2006 of The Building Regulations.
CK60 boilers may be fired by Natural gas, Class D oil or dual fuel burners with 2-stage control. Modulating burners are optionally available.
- Seasonal efficiency of over 84% gives compliance with ADL2B 2006 without the need for additional heating credits
- Compact heat exchanger gives small footprint relative to output
- Delivered as a ready-assembled block
- Wide range of 2-stage gas and oil, dual-fuel and modulating gas burners available
PLEASE NOTE
RELATED PRODUCTS
- Matching calorifier for indirect wholesome hot water
| Model | Output (kW) | Depth (mm) | Height (mm) | Width (mm) | Flue connection size(mm) | Flow connection size | Boiler seasonal efficiency(%) | Return connection size |
| CK6008B | 600 | 1620 | 1428 | 1150 | 350 | DN100 | 84 | DN100 |
| CK6009B | 690 | 1800 | 1428 | 1150 | 350 | DN100 | 84 | DN100 |
| CK6010B | 780 | 1980 | 1428 | 1150 | 350 | DN100 | 84 | DN100 |
| CK6011B | 870 | 2160 | 1428 | 1150 | 400 | DN100 | 84 | DN100 |
| CK6012B | 960 | 2340 | 1428 | 1150 | 400 | DN100 | 84 | DN100 |
| CK6013B | 1060 | 2520 | 1428 | 1150 | 400 | DN100 | 84 | DN100 |
| CK6014B | 1160 | 2700 | 1428 | 1150 | 400 | DN100 | 84 | DN100 |