clyde Energy Solutions

Unical Trio

Unical Trio Unical Trio

Enlarge

The Unical Trio range of three-pass, high efficiency steel boilers offers configurations from 110kW to 1900kW output and a wide range of fuel options.

The three pass design maximises the heat output per unit of fuel and allows high output from a small footprint boiler typically 1mW per 0.7m³ of combustion chamber size. Whereas a condensing boiler reuses the latent heat of condensation, the trio re-evaporates the condensate to protect the steel boiler from acid corrosion.

Compared to a reverse flame steel boiler there is less metallurgical stress on the combustion chamber and NOx emissions c

  • Three-pass boiler design and large combustion chamber volume increases efficiency and reduces N0x emissions
  • Efficiency of up to 91.6% (ncv)
  • Very low stand-by losses
  • Wide range of 2-stage gas and oil, dual-fuel and modulating gas burners available.
  • Patented anti-condensation design permits return water temperatures of 36oC when firing with oil and 46owhen firing with gas
Model Output (kW) Depth (mm) Height (mm) Width (mm) Flue connection size(mm) Flow connection size Boiler Seasonal Efficiency(%) Return connection size
TRIO-110 110 885 1272 820 DN180 DN50 82 DN50
TRIO-150 150 1145 1272 820 DN180 DN50 82 DN50
TRIO-185 185 1080 1372 860 DN180 DN65 82 DN65
TRIO-225 225 1210 1372 860 DN180 DN65 82 DN65
TRIO-300 300 1275 1542 890 DN225 DN80 82 DN80
TRIO-380 380 1470 1542 890 DN225 DN80 82 DN80
TRIO-500 500 1605 1835 920 DN250 DN100 82 DN100
TRIO-630 630 1800 1835 920 DN250 DN100 82 DN100
TRIO-730 730 1995 1835 920 DN250 DN100 82 DN100
TRIO-840 840 2115 1622 1122 DN250 DN100 82 DN100
TRIO-1100 1100 2282 1732 1462 DN350 DN150 82 DN150
TRIO-1320 1320 2652 1732 1462 DN350 DN150 82 DN150
TRIO-1600 1600 2692 1892 1622 DN400 DN175 82 DN175
TRIO-1900 1900 3014 1892 1622 DN400 DN175 82 DN175

Clyde Energy Solutions Ltd Units 13-14, Charlwoods Road, East Grinstead, West Sussex RH19 2HU | T 01342 305550 | E info@clyde4heat.co.uk